Permit: T06CM01371

Parcel: 131090620


Addresses:

5791 E 24TH ST #01

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
10/16/2006 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
10/09/2006 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. STAPLE N.M CABLE PER N.E.C -- I.R.C
AT PANEL & AT SWITCHES.
2. TIGHTEN ALL GROUNDING SCREWS.
3. SEAL UNUSED OPENINGS AT PANEL.
4. REMOVE CROSSOVER LINK BETWEEN NEUTRAL & GROUNDING BUS.
5. BOND GROUNDING BUS BAR TO PANEL ENCLOSURE.
6. SEAL OPENING AT SERVICE EQUIP.