Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/16/2006 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 10/09/2006 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. STAPLE N.M CABLE PER N.E.C -- I.R.C AT PANEL & AT SWITCHES. 2. TIGHTEN ALL GROUNDING SCREWS. 3. SEAL UNUSED OPENINGS AT PANEL. 4. REMOVE CROSSOVER LINK BETWEEN NEUTRAL & GROUNDING BUS. 5. BOND GROUNDING BUS BAR TO PANEL ENCLOSURE. 6. SEAL OPENING AT SERVICE EQUIP. |