Inspection History Details
Inspection Status: Approved
Inspection History: BUILDING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/04/2008 | BUILDING - FINAL | Approved | IVRS - Inspection :* | |
| 07/29/2008 | BUILDING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) WATER LINE DEPTH AT SOUTH HOSE BIB NEEDS TO BE 12" DEEP 2) NEED TO INSULATE ALL HOLES AND SPACES IN EXTERIOR BLK WALL 3) NEED TO LOWER CLEANOUT IN FRONT YARD AND APPROVED COVER 4) COMPLETE CLEANOUT ON EXT. WEST WALL 5) TERMINATION OF TPR AND CONDENSATION LINE NEED 90 DEGREE 6) POST ADDRESS WERE VISIBLE FROM STREET 7) NEED GFI RECEPTACLE AT HVAC UNIT |
|
| 05/30/2008 | BUILDING - FINAL | Not ready for Inspection | IVRS - Inspection :* |