Inspection History Details
Permit: T06CM01341
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/11/2007 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* | |
| 04/04/2007 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* COMPLETELY PAINT ALL EXPOSED PVC W/LATEX PAINT IF YOU CAN READ THE LETTERING, THEN IT IS NOT PAINTED GOOD ENOUGH. TAPE WHITE WIRE AT CONDENSOR DISCONNECT |
|
| 03/28/2007 | MECHANICAL - FINAL | Partial Approval | PAINT EXPOSED PVC W/LATEX PAINT & SUPPORT PROPERLY I.D UNITS SEAL TITE BROKEN TURN FUSES SO THEY CAN BE IDENTIFIED WHITE WIRE IN ELEC. DISCONNECTS CONDENSOR PAD MUST SIT ON TOP OF GRADE ANCHOR CONDENSOR TO PAD |
|
| 02/13/2007 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* 1. PROVIDE AIR BALANCE REPORT 2. MARK UNIT DATA PLATES WITH PROPER HEAT STRIP INSTALLED & FUSE ACCORDINGLY. 3. BE SURE ALL T-TOPS HAVE SCREEN EXCEPT DRYER VENTS. 4. BE SURE ALL CONNECTIONS TO EQUIPMENT ARE MADE. |