Permit: T06CM01341

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
04/11/2007 MECHANICAL - FINAL Approved IVRS - Inspection :*
04/04/2007 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
COMPLETELY PAINT ALL EXPOSED PVC W/LATEX PAINT
IF YOU CAN READ THE LETTERING, THEN IT IS NOT PAINTED GOOD ENOUGH.
TAPE WHITE WIRE AT CONDENSOR DISCONNECT
03/28/2007 MECHANICAL - FINAL Partial Approval PAINT EXPOSED PVC W/LATEX PAINT & SUPPORT PROPERLY
I.D UNITS
SEAL TITE BROKEN
TURN FUSES SO THEY CAN BE IDENTIFIED
WHITE WIRE IN ELEC. DISCONNECTS
CONDENSOR PAD MUST SIT ON TOP OF GRADE
ANCHOR CONDENSOR TO PAD
02/13/2007 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
1. PROVIDE AIR BALANCE REPORT
2. MARK UNIT DATA PLATES WITH PROPER HEAT STRIP INSTALLED & FUSE ACCORDINGLY.
3. BE SURE ALL T-TOPS HAVE SCREEN EXCEPT DRYER VENTS.
4. BE SURE ALL CONNECTIONS TO EQUIPMENT ARE MADE.