Permit: T06CM01341

Inspection Status: Approved

Inspection History: PLUMBING - INTERMEDIATE

Date Description Inspector Results Comments
10/04/2006 PLUMBING - INTERMEDIATE Approved IVRS - Inspection :*
1. REVISED P1.4 MARKED AS REDLINE 10/02/06 AND INITIALED BY ME, INCLUDES "OPTION - 3 BEDROOM 4" DUAL ROUGH.

PEX OK
DWV OK
TUBS OK
FLANGES OK
OK TO COVER ALL AREAS

I WILL STILL NEED A LETTER ACKNOWLEDGING MULTIPLE MAT'L TYPES PEX, PROPRESS, SOLDERED COPPER.
10/02/2006 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
PROVIDE LETTER FROM ARCHITECT ALLOWING MULTIPLE MATERIAL TYPES IE: PEX, COPPER, PROPRESS
10/02/2006 PLUMBING - INTERMEDIATE Not ready for Inspection INTERMEDIATE NOT INSTALLED PER PLAN
NO REDLINES ON SITE.
10/02/2006 PLUMBING - INTERMEDIATE Not ready for Inspection PLAN REVIEWED ON 6/22/06 DOES NOT INCLUDE PLUMBING CHANGES. YOU ARE REQUESTING INTERMEDIATE INSPECTION, HOWEVER, YOU STILL HAVE UNRESOLVED ROUGH/SOIL ISSUES; IE. NO APPROVED PLAN. UNDERGROUND CHANGES AFFECT INTERMEDIATE LAYOUT. NO REDLINES FOR INTERMEDIATE CHANGES ON SITE.
09/27/2006 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
1. I LEFT ANOTHER COPY OF PIMA COUNTY ADDRESS DISPLAY REQUIREMENTS WITH COPY OF INSPECTION REPORT.
2. 95% OF POSTED ADDRESS MISSING. UNABLE TO TELL WHICH LOT IS 2466 E. BLUE DIAMOND DR.
09/26/2006 PLUMBING - INTERMEDIATE Cancelled IVRS - RI canceled
04/20/2006 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. SECOND FLOOR ROUGH OK
WATER TEST ONE RISER TO TEN FEET OK
2. CONTRACTOR TO WRAP ALL EXPOSED PIPE PRE-POUR ROUGH/SOIL REINSPECTED COMPLETE.
04/17/2006 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. OWNER TOOK OPTION FOR 1ST FLOOR BATHROOM
LOCATION OF UPSTREAM MANHOLD MANDATES THE USE OF A BACKWATER VALVE FOR 1ST FLOOR PLUMBING.
1ST FLOOR PLUMBING OK TO COVER SUBJECT TO APPROVAL OF REVISED APPROVED PLAN.
NEED TO SEE SECOND FLOOR PLUMBING - UNDERGROUND.
04/14/2006 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
1. PROVIDE ELEVATION OF FLOOR LEVEL AND UPSTREAM MANHOLE.