Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit: T06CM01341

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
05/11/2007 ELECTRIC - FINAL Approved IVRS - Inspection :*
05/09/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. PANEL DIRECTORY NOT CORRECT -- NEC 408.4
2. RANGE CKT, RECEPT, BREAKER UNDERSIZED -- NEC 422.10 A

ALL ELSE OK (PREVIOUS CORRECTIONS)
05/01/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. STILL NEED TO PAY PREVIOUS REINSPECTION FEE
2. AC BRANCH CKT'S STILL UNDERSIZED PER DATA PLATES
3. REMOVE SITE ELECTRICAL WIRING AND RACEWAY FROM THIS UNIT.

THERE WILL BE ANOTHER FEE IF NOT CORRECT NEXT TIME.
04/30/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. MASTER SHOWER TRIM MISSING
2. SOUTH BEDROOM LIGHTING STILL NOT ARC FAULT (CANS)
3. HAVE UNDERSIZED CKT TO ROOFTOP UNITS PER DATA PLATE MARKING.
4. STILL NEED TO PAY REINSPECTION FEE
5. FINAL SUBJECT TO SITE ELECTRICAL PERMIT/FED FROM THIS UNIT.
04/27/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. NEED TO FINISH CORRECTION #6, #7, #8 FROM PREVIOUS INSPECTION
2. CHECK TO MAKE SURE AC DATA PLATES ARE CORRECTLY IDENTIFIED

NEED TO PAY REINSPECTION FEE

3. HAVE SITE ELECTRIC POWER FROM THIS UNIT, NO PER PLANS
03/28/2007 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
FINISH ALL CORRECTIONS BEFORE INSPECTION
02/13/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. SECURE EXTERIOR CONDENSOR TO SLAB -
NEC 110.3B, 110.13
2. PROPERLY IDENTIFY WHITE USED AS HOT AT BOTH ENDS DISCONNECT TO CONDENSOR - NEC 310.12C
3. REMOVE ALL OBSTRUCTIONS IN FRONT OF ELECTRICAL EQUIPMENT AND RECEPTACLES FOR INSPECTION (ELEVATOR CONTROL, PANEL, WALLS, ETC)
4. RANGE ANTI-TIP DEVICE NOT WORKING - NEC 110.3B
5. INSTALL DISHWASHER CORD
6. 2ND FLOOR SMOKE DETECTOR NEED 36" MIN. TO HVAC VENT
7. 3RD FLOOR BEDROOM LIGHTING TO HAVE ARC FAULT PROTECTION -- 210.12
8. CHECK BULB WATTAGE IN SHOWER CANS WITH SHOWER TRIM.
9. AT ROOFTOP UNITS - IDENTIFY DATA PLATE, ANY HEAT STRIPS? - MARK LABEL. ALSO, SEE CORRECTION #2 THIS PAGE AND PROPERLY FUSE UNITS.
10. NEED SMOKE DETECTOR ON 4TH LEVEL?
11. PROVIDE DISCONNECTING MEANS FOR HOT WATER TANK AND BARBEQUE AS REQUIRED BY NEC 422.31B

PARTIAL INSPECTION ONLY