Permit: T06CM01341
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/21/2007 | ELECTRIC - INTERMEDIATE | Approved | ||
| 10/02/2006 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK ELECTRICAL COVER -- ALL INTERIOR. |
|
| 09/29/2006 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. NEED TO USE PROPER CRIMP TOOL FOR CRIMPS SLEEVES USED ON GROUND TERMINATIONS IN BOXES -- NEC 110.3 2. ONLY ONE NEUTRAL ALLOWED UNDER SAME TERMINATION IN SUB PANEL -- NEC 408.21 3. LOW VOLTAGE WIRING OUTSIDE THE WALL IN SOME AREAS AND NEEDS NAIL PLATES AS REQUIRED -- NEC 300.5 4. PROVIDE CONNECTOR FOR FLOOR BOXES -- NEC 314.17C AND BATH FANS. |
|
| 09/26/2006 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. PULL FEEDER & WIRE IN SUB-PANEL 2. USE PROPER CRIMP TOOL FOR CRIMP SLEEVES -- NEC 110.3 3. IDENTIFY WHITE USED AS HOT IN DEADEND 3 WAY CKT'S AND AS NEEDED -- NEC 310.12 (C) 4. DRYWALL TO BE REMOVED FOR WALL INSPECTION. 5. RECEPTACLE REQUIRED ALONG OPEN RAILING -- NEC 210.52 6. HAVE OPEN WIRING @ 2ND LEVEL ENTRY? 7. BATH FAN ABOVE FINISHED CEILING 8. PROVIDE NAIL PLATES FOR ALARM WIRING AS NEEDED AND RUN WIRING ON INSIDE OF WALL LIKE 120V WIRINIG |