Permit: T06CM01341

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
05/21/2007 ELECTRIC - INTERMEDIATE Approved
10/02/2006 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK ELECTRICAL COVER -- ALL INTERIOR.
09/29/2006 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. NEED TO USE PROPER CRIMP TOOL FOR CRIMPS SLEEVES USED ON GROUND TERMINATIONS IN BOXES -- NEC 110.3
2. ONLY ONE NEUTRAL ALLOWED UNDER SAME TERMINATION IN SUB PANEL -- NEC 408.21
3. LOW VOLTAGE WIRING OUTSIDE THE WALL IN SOME AREAS AND NEEDS NAIL PLATES AS REQUIRED -- NEC 300.5
4. PROVIDE CONNECTOR FOR FLOOR BOXES -- NEC 314.17C AND BATH FANS.
09/26/2006 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. PULL FEEDER & WIRE IN SUB-PANEL
2. USE PROPER CRIMP TOOL FOR CRIMP SLEEVES -- NEC 110.3
3. IDENTIFY WHITE USED AS HOT IN DEADEND 3 WAY CKT'S AND AS NEEDED -- NEC 310.12 (C)
4. DRYWALL TO BE REMOVED FOR WALL INSPECTION.
5. RECEPTACLE REQUIRED ALONG OPEN RAILING -- NEC 210.52
6. HAVE OPEN WIRING @ 2ND LEVEL ENTRY?
7. BATH FAN ABOVE FINISHED CEILING
8. PROVIDE NAIL PLATES FOR ALARM WIRING AS NEEDED AND RUN WIRING ON INSIDE OF WALL LIKE 120V WIRINIG