Permit: T06CM01340

Parcel: 126011240


Addresses:

963 N DESERT AV

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
04/23/2007 ELECTRIC - FINAL Approved IVRS - Inspection :*
OK FINAL
04/05/2007 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
OK ALL OTHER ITEMS EXCEPT PLAN PANEL REVISION

1. PLANS DO NOT REFLECT INSTALLATION -- ALSO NEED CITY STAMP OR WILDAN
04/03/2007 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1. JUNCTION BOX BY PANEL - GROUND ENCLOSURE & INSTALL MISSING LOCKNUT
2. FINISH PREVIOUS ITEMS 2, 3, 4 AND 8
03/26/2007 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
1) A BOX IS NEEDED FOR BATH LIGHTS-THERE ARE ALSO EXPOSED CONDUCTORS NOTCHED INTO DRYWALL
2) INSTALL CONDUCTORS UNDER TERMINAL SCREWS-AT LEAST 3/4 OF A TURN
3) BOXES MORE THAN 1/4" FROM BOX TO SURFACE NEED AN APPROVED EXTENDER RING 314.20 FLUSH AT COMBUSTIBLES
4) GROUNDING EQUIPMENT CONDUCTOR TO BE AS PER 250.122-A/C
5) NEED DISCONNECTING MEANS FOR WATER HEATER AND TIGHTEN LOOSE FITTINGS
6) ANTI-OXIDE COMPOUND NEEDED FOR ALL ALUMINUM CONDUCTORS-DISCONNECTS
7) CORRECTLY LABEL BREAKER-NO ABREVATIONS 408.4
8) PLANS NOT REFLECTIVE OF WORK AND LOADS DONE AT POOL ROOM