Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/23/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* OK FINAL |
|
| 04/05/2007 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* OK ALL OTHER ITEMS EXCEPT PLAN PANEL REVISION 1. PLANS DO NOT REFLECT INSTALLATION -- ALSO NEED CITY STAMP OR WILDAN |
|
| 04/03/2007 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1. JUNCTION BOX BY PANEL - GROUND ENCLOSURE & INSTALL MISSING LOCKNUT 2. FINISH PREVIOUS ITEMS 2, 3, 4 AND 8 |
|
| 03/26/2007 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) A BOX IS NEEDED FOR BATH LIGHTS-THERE ARE ALSO EXPOSED CONDUCTORS NOTCHED INTO DRYWALL 2) INSTALL CONDUCTORS UNDER TERMINAL SCREWS-AT LEAST 3/4 OF A TURN 3) BOXES MORE THAN 1/4" FROM BOX TO SURFACE NEED AN APPROVED EXTENDER RING 314.20 FLUSH AT COMBUSTIBLES 4) GROUNDING EQUIPMENT CONDUCTOR TO BE AS PER 250.122-A/C 5) NEED DISCONNECTING MEANS FOR WATER HEATER AND TIGHTEN LOOSE FITTINGS 6) ANTI-OXIDE COMPOUND NEEDED FOR ALL ALUMINUM CONDUCTORS-DISCONNECTS 7) CORRECTLY LABEL BREAKER-NO ABREVATIONS 408.4 8) PLANS NOT REFLECTIVE OF WORK AND LOADS DONE AT POOL ROOM |