Permit: T06CM01340

Parcel: 126011240


Addresses:

963 N DESERT AV

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
04/23/2007 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
01/30/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK ROUGH ELECTRIC
*RECEIVED LETTER FOR NM CABLE
01/16/2007 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
1. PROTECT CONDUCTORS FROM SCREWS INSIDE OF
BOXES 314.23
2. PROTECT CABLES AT SDOD
3. BOX IS OVERFILLED
4. SUPPORT NM CABLE WITHIN 12" OF EXHAUST FANS AND AN APPROVED CONNECTOR IS NEEDED.
5. SUPPORT NM CABLE WITHIN 12" OF LIGHT BOXES
6. SCHEDULE 80 CONDUIT IS NEEDED FOR ABOVE GROUND USAGE.
7. USE APPROVED SIZED PULL BOX ABOVE PANEL 312.6
8. USE SCREWS OTHER THAN DRYWALL TO ANCHOR TO BLOCK ALSO, MAKE UP BOX & GROUND
9. MAINTAIN CLEARANCE AND ACCESSIBILITY TO BOXES & DISCONNECTS ABOVE BATHROOM.
10. PLEASE PROVIDE LETTER AUTHORIZING USE OF NM CABLE
11. PLANS DO NOT REFLECT FAN COIL ABOVE BATH CEILING REVISE FOR LOCATION & LOADS.