Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/23/2007 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 01/30/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK ROUGH ELECTRIC *RECEIVED LETTER FOR NM CABLE |
|
| 01/16/2007 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* 1. PROTECT CONDUCTORS FROM SCREWS INSIDE OF BOXES 314.23 2. PROTECT CABLES AT SDOD 3. BOX IS OVERFILLED 4. SUPPORT NM CABLE WITHIN 12" OF EXHAUST FANS AND AN APPROVED CONNECTOR IS NEEDED. 5. SUPPORT NM CABLE WITHIN 12" OF LIGHT BOXES 6. SCHEDULE 80 CONDUIT IS NEEDED FOR ABOVE GROUND USAGE. 7. USE APPROVED SIZED PULL BOX ABOVE PANEL 312.6 8. USE SCREWS OTHER THAN DRYWALL TO ANCHOR TO BLOCK ALSO, MAKE UP BOX & GROUND 9. MAINTAIN CLEARANCE AND ACCESSIBILITY TO BOXES & DISCONNECTS ABOVE BATHROOM. 10. PLEASE PROVIDE LETTER AUTHORIZING USE OF NM CABLE 11. PLANS DO NOT REFLECT FAN COIL ABOVE BATH CEILING REVISE FOR LOCATION & LOADS. |