Permit: T06CM01339

Inspection Status: Approved

Inspection History: FRAMING

Date Description Inspector Results Comments
11/02/2006 FRAMING Approved IVRS - Inspection :*
10/24/2006 FRAMING Partial Approval IVRS - Inspection :*
FIRE ASSEMBLY ABOVE TRUSSES OK
10/23/2006 FRAMING Not ready for Inspection IVRS - Inspection :*
FIRESTOP BETWEEN RAFTERS
10/19/2006 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999*
NEED FIRESTOP SYSTEM
DO NOT TAPE JOINTS OR PENETRATIONS ABOVE CEILING.
09/26/2006 FRAMING Partial Approval IVRS - Inspection :*
1. WEST FIREWALL HAS HOLES IN EXT ROCK
2. HOW TO FIREBLOCK SHAFT/RATE SHAFT
3. NO P-RINGS ALLOWED IN RATED WALLS
05/19/2006 FRAMING Partial Approval IVRS - Inspection :*
FIREWALL ONLY