Inspection History Details
Permit: T06CM01338
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/04/2007 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* OK FOR FINAL CORRECTIONS HAVE BEEN MADE |
|
| 03/28/2007 | MECHANICAL - FINAL | Partial Approval | I.D UNITS ONE UNIT DOUBLE TRAPPED |
|
| 03/16/2007 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. DO NOT USE WHITE WIRE TO POWER AC UNITS. TIGHTEN ALL LOOSE SEAL TITE CONNECTIONS. CONDUIT NOT SUPPORTED PROPERLY. 2. EACH A/C UNIT MUST BE INDIVIDUALLY TRAPPED. 3. PERMANENTLY I.D DATA PLATES WITH THE PROPER HEAT STRIP INSTALLED & FUSE ACCORDINGLY. PERMANENTLY I.D AC UNITS. 4. PAINT ALL EXPOSED PVC W/LATEX PAINT 5. REPAIR ALL SMASHED T-TOPS |