Permit: T06CM01338

Inspection Status: Approved

Inspection History: MECHANICAL - INTERMEDIATE

Date Description Inspector Results Comments
10/11/2006 MECHANICAL - INTERMEDIATE Approved IVRS - Inspection :*
10/05/2006 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection :*
NOTE! THERE WILL BE 2 INTERMEDIATE INSP.'S PROVIDED
3 OR MORE WILL BE CHARGED A REFEE ON FUTURE INSPECTIONS.

2ND FLOOR
1. WRAP 3 10X10X12" CANS (SUPPLY) ON 2ND FLOOR
TOP FLOOR
2. RETURN AIR W/OUTSIDE AIR, SECURE UP INTO FRAMING
WHERE IS OUTSIDE AIR ON 2ND UNIT?
4" FLEX, OUTSIDE AIR INTAKE NOT SECURED UP INTO ROOF FLASHINGS.
10/03/2006 MECHANICAL - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
- 1ST FLOOR EXHAUST DUCT NOT TERMINATED
- 2ND FLOOR EXHAUST MISSING BACKDRAFT DAMPER.
- PROVIDE BACKING AROUND ALL CEILING BOXES
- PROVIDE CONDENSATE DRAIN.
10/01/2006 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection :*