Inspection History Details
Permit: T06CM01338
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/11/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 05/01/2007 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* OK FINAL PENDING REFEE PAYMENT AND SITE PERMIT |
|
| 04/12/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* ON ROOF, PER UNIT DATA PLATE 1. HAVE UNDERSIZED CONDUCTORS TO POWER UNITS 44AMP MIN. CKT AMP 2. HAVE WRONG FUSE SIZES 3. STILL NEED LIGHT IN LIVING ROOM ALSO, ALL SITE WORK ELECTRICAL MUST BE PERMITTED, INSPECTED AND APPROVED BEFORE ANY OF THESE UNITS WILL RECEIVE A FINAL ELECTRICAL APPROVAL |
|
| 04/11/2007 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* CORRECTIONS NOT COMPLETE/WORK IN PROGRESS NEED TO PAY REINSPECTION FEE UNLOCK ELEVATOR DISCONNECTS |
|
| 03/28/2007 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* FINISH CORRECTIONS (ALL) |
|
| 03/16/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. MULTIWIRE BRANCH CKTS TO TERMINATE ON SEPARATE PHASES IN PANEL. 2. ALL ELEVATOR ENCLOSURES NEED TO BE PROPERLY GROUNDED AND DISCONNECTS SPECIFICALLY IDENTIFIED AS TO WHAT THEY DISCONNECT. ALSO, NEED CONNECTOR FOR ROMEX ENTERING DISCONNECT. 3. DOWNSTAIRS BEDROOM NEEDS LIGHT OR SWITCHED RECEPTACLE AND ARC FAULT PROTECTION FOR ALL OUTLETS (LIGHTS, RECEPTACLES, SMOKES) 4. PROVIDE DISCONNECTING MEANS FOR HOT WATER HEATER 5. NEED LIGHT 2ND LEVEL LIVING ROOM 6. ALL WIRING TO LOW VOLTAGE LIGHTING NEEDS PROPER J-BOX ON ROOF TOP 7. UNITS DATA PLATES ARE NOT IDENTIFIED (HEAT STRIPS) CHECK FOR PROPER CONDUCTOR SIZE AND FUSE SIZE - IT APPEARS TO BE WRONG. FLEX TO BE STRAPPED WITHIN 12" OF TERMINATIONS AND RUN ALONG ROOF DON'T STRETCH ACROSS. 8. ENSURE PANEL DIRECTORY CORRECTLY IDENTIFIED. |