Inspection History Details
Inspection Status: Approved
Inspection History: FRAMING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/13/2006 | FRAMING | Approved | IVRS - Inspection :* | |
| 06/06/2006 | FRAMING | Not ready for Inspection | IVRS - Inspection :* | |
| 05/26/2006 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) NO REFEE ASSESSED AT THIS TIME 2) SECURE ROMEX TO WITHIN 12" ALL BOXES 3) 10 POUND GAS PRESSURE TEST REQUIRED 4) EVAP COOLER TO BE REMOVED 5) KITCHEN ELECTRIC CIRCUITS TO BE 20 AMP #12 WIRE 6) INSTALL H20 HEATER CABINET, PTR LINE AND FLU PIPE 7) PLAN CALLS FOR 3/4" GAS LINE TO ROOF UNIT 8) ELECTRIC NOT RUN TO ROOF TOP UNIT 9) ALL ELECTRIC EXPOSED BELOW 8' TO BE IN CONDUIT 10) ALL ELECTRIC J-BOXES TO BE ACCESSIBLE 11) INSTALL 220 VOLT WIRES GARAGE IN CONDUIT 12) MAKE UP ALL GROUNDS ELECTRIC BOXES 13) COMPLETE EXHAUST HOOD DUCT KITCHEN 14) SINK TRAP ARM INADEQUATE SLOPE 15) H20 TEST DWV THROUGH ROOF 16) SECURE PLASTIC ELECTRIC BOXES TO WALLS 17) SLIP FITTING NOT ALLOWED DRAIN TUB-MUST BE GLUED FITTING 18) ALL H20 LINES BELOW SLAB TO BE REROUTED OVER HEAD 19) STOPPED INSPECTION 20) COMPLETE ALL AND RECALL |
|
| 05/16/2006 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) INCOMPLETE-RECALL WHEN READY |
|
| 03/30/2006 | FRAMING | Not ready for Inspection | IVRS - Inspection :* 1) ALL INTERMEDIATE MUST BE COMPLETE BEFORE FRAMING INSPECTION |
|
| 03/29/2006 | FRAMING | Not ready for Inspection | IVRS - Inspection :* 1) LOCKED-NO ACCESS 2) PLANS/PERMIT ?? RECALL |