Permit: T06CM01334

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
06/15/2007 PLUMBING - FINAL Approved IVRS - Inspection :*
06/13/2007 PLUMBING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) CHINA BOWL CAPS
2) PROVIDE LISTINGS REQUIRED PER UPC SEC 401.1 FOR TUBS, SHOWER VALVES AND PEDESTAL LAVITORIES
3) THESE FIXTURES DO NOT APPEAR TO MEET NATIONALLY RECOGNIZED STANDARDS AND HAVE NO IDENTIFYING MARKINGS
05/11/2007 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
1) DO NOT REQUEST FINAL INSPECTION UNTIL INTERMEDIATE HAS BEEN APPROVED. CONTINUED NOT READY INSPECTIONS WILL RESULT IN REINSPECTION FEES. SECTION 1.2 IN UPC INSTALLATION STANDARD #4 REQUIRES INSPECTION OF SHOWER LINER PRIOR TO TILE. NOTE: WATER LEVEL IS DOWN 1" BELOW FLOOD LEVEL. REMOVE TILE FOR INSPECTION
05/01/2007 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
CALL FOR INTERMEDIATE INSPECTION, PROVIDE PROOF THAT LINER WAS PROPERLY INSTALLED. PROVIDE WATER TEST. FOR FINAL ALL GARDEN TUBS SHALL BE FULL OF WATER FOR INSPECTION.
04/19/2007 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
NOT READY FOR FINAL
INTERMEDIATE IS NOT COMPLETE