Permit: T06CM01334

Inspection Status: Approved

Inspection History: ELECTRIC - PROGRESS

Date Description Inspector Results Comments
10/31/2006 ELECTRIC - PROGRESS Approved IVRS - Inspection :*
10/26/2006 ELECTRIC - PROGRESS Not ready for Inspection IVRS - Inspection :*
1.TIGHTEN LOOSE CONNECTORS AT SUB-PANEL AND STRAP CABLES WITHIN 12" OF PANEL.
2. PLEASE UNCOVER WALLS INSIDE ELEVATOR SHAFT TO INSPECT WIRING.
3. SECURE NM CABLE TO BOXES/METAL
4. SUPPORT NM CABLES WITHIN 12" OF BOXES & CANS.
5. SUPPORT VDV CABELING DOWN WALLS.
6. SECURE NM CABLE AT PATCH & PANEL BOX.
7. SECURE SE CABLE TO WALLS TO ALL-IN-ONE.