Inspection History Details
Permit: T06CM01331
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/22/2007 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 11/16/2006 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK INTERIOR ELECTRICAL COVER |
|
| 11/07/2006 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. NEUTRALS ON 3 WIRE HOME RUNS NEED TO BE PIGTAILED NEC 210? 2. MOVE DRYWALL AWAY FROM WALLS SO I CAN SEE WALLS. 3. MAX 12' BETWEEN RECEPTACLES ALONG WALL -- NEC 210.52 A1 4. FINISH LOW VOLTAGE WIRING (ALL) 5. SMOKE DETECTORS NEED TO BE MINIMUM 3 FEET FROM HVAC VENTS -- SUPPLY OR RETURN REINSPECTION FEE WILL BE CHARGED IF CORRECTIONS NOT COMPLETE NEXT INSPECTION. |
|
| 11/01/2006 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* DO NOT CALL BEFORE READY |
|
| 10/31/2006 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* |