Permit: T06CM01329

Parcel: 141095220

Inspection Status: Approved

Inspection History: FRAMING

Permit Number - T06CM01329

Inspection Description - FRAMING

Inspection Status - Approved

Date Description Inspector Results Comments
01/18/2007 FRAMING Approved IVRS - Inspection :*
01/16/2007 FRAMING Not ready for Inspection IVRS - Inspection :*
1) STUCCO LATHE DEGRADED BY SUN EXPOSURE
01/03/2007 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) OUTSIDE HOSE BIB REQUIRED ANTI-SIPHON VALVE
2) NO TRACER ON YARD WATER
3) TOILET ABOVE POWDER ROOM NOT PROPERLY VENTED
4) STAIR RISE EXCEEDS 3/8" DIFFERENCE AND 7 3/4 RISE BOTH STAIRS
5) PUT HANGERS ON TRUSSES
6) NAIL PROTECT WIRES
7) NAIL SHEARWALL LADDER BACK TO WALL
8) NAIL PROTECT PLUMBING
9) SUPPLY TO FIRST FLOOR KINKED REQUIRES 1 DUCT ?
10) AC SECONDARY DRAIN MUST BE IN CONSPICOUS LOCATION
11) MISSING ANCHOR BOLT DEN
12) SEAL VAPOR BARRIER
13) BAD GAUGE-NO GAS TEST