Permit: T06CM01325

Parcel: 131100640


Addresses:

5617 E 24TH ST

Inspection Status: Approved

Inspection History: PLUMBING - GAS PRESSURE TEST

Date Description Inspector Results Comments
05/15/2006 PLUMBING - GAS PRESSURE TEST Approved IVRS - Inspection :*
12 PSI TEST FROM METER UNDERGROUND UP AT BUILDING TO DRYER, WATER HEATER & EXISTING TO STOVE ONLY. APPROVED.
METER IS NOT LOCKED OUT BY S.W. GAS OWNER TO VERIFY NO LEAKAGE AT METER CONNECTION AND AT ALL APPLIANCE CONNECTIONS WHEN GAS IS TURNED ON.
05/12/2006 PLUMBING - GAS PRESSURE TEST Not ready for Inspection IVRS - Inspection :*
1. PRESSURE TEST SHALL HOLD WITH NO PRESSURE LOSS.
NOT READY
2. PROVIDE CORRECT COMBUSTION AIR FOR WATER HEATER.
3. THERE SHALL BE NO FUTURE TEE CONNECTIONS IN GAS PIPING SYSTEM WITHOUT A CITY APPROVED PLAN.
NOT READY.