Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - UNDERGROUND
Permit Number - T06CM01322
Inspection Description - ELECTRIC - UNDERGROUND
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/02/2007 | ELECTRIC - UNDERGROUND | Approved | IVRS - Inspection :* | |
01/26/2007 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* OK TO COVER RACEWAYS FOR WEST SIDE SIGNAGE/SERVICES (4 ALONG 1ST AV) AND IRRIGATION -- INSTALL WARNING RIBBON IN ALL SERVICE TRENCHES MINIMUM 12" ABOVE SERVICE RACEWAY WHEN YOU BACKFILL NEC 300.5 D3 |
|
01/17/2007 | ELECTRIC - UNDERGROUND | Not ready for Inspection | IVRS - Inspection :* | |
12/19/2006 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* | |
12/14/2006 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* OK TO CONTINUE RACEWAYS FOR SITE LIGHTING UNDERGROUND - WILL CALL POLE BASES IN BEFORE YOU POUR |
|
12/08/2006 | ELECTRIC - UNDERGROUND | Not ready for Inspection | IVRS - Inspection :* INSPECTION MADE 12/7/06 |
|
12/07/2006 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* OK TO CONTINUE ON SITE LIGHTING, RACEWAYS TO BE 24" & 18" MINIMUM. CALL FOR TUESDAY INSPECTION. |