Permit: T06CM01311

Parcel: 141015590

Inspection Status: Approved

Inspection History: FRAMING

Permit Number - T06CM01311

Inspection Description - FRAMING

Inspection Status - Approved

Date Description Inspector Results Comments
08/14/2006 FRAMING Approved IVRS - Inspection :*
08/04/2006 FRAMING Partial Approval IVRS - Inspection :*
1) NEED BLOCKING AT SIDES OF CHIMNEY
2) CHASE TO PREVENT FIRE GOING INTO FURR DOWNS EACH SIDE OF CHIMNEY
3) OK TO INSULATE AND SHEETROCK OTHER AREAS THAN CHIMNEY
08/03/2006 FRAMING Partial Approval IVRS - Inspection :*
1. FIREBLOCK TOP SIDES OF CHIMNEY CHASE
2. BLOCK REGISTER BATH #2
3. IF COUNTER WEST WALL OF KITCHEN EXTENDS TO SOUTH CORNER AN ADDITIONAL RECEP. WILL BE REQUIRED.
4. SUPPORT 4 GANG BOX
5. PLAN SHOWS BAR SINK IN BONUS BEDROOM
6. NEED 1" CLEAR TO FIREPLACE B-VENT
7. PURPOSE OF 10-2 WIRE IN WALL NEAR BATH OF BONUS BEDROOM?