Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - INTERMEDIATE
Permit Number - T06CM01309
Inspection Description - PLUMBING - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/17/2006 | PLUMBING - INTERMEDIATE | Approved | IVRS - Inspection :* | |
08/15/2006 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) FURNACE ROOM WILL REQUIRE COMBUSTION/RELIEF AIR IN DOOR 2) EXTEND WALL HEATER VENT THRU CEILING 3) DOES FURNACE ROOM NEED PVC VENT ? 4) ABS LEAK UNDER MASTER SHOWER-SUPPLY OK |