Permit: T06CM01301


Addresses:

7884 E SPEEDWAY BL

Inspection Status: Approved

Inspection History: ELECTRIC - OUTDOOR LIGHTING

Date Description Inspector Results Comments
09/29/2006 ELECTRIC - OUTDOOR LIGHTING Approved IVRS - Inspection :*
07/18/2006 ELECTRIC - OUTDOOR LIGHTING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. POLE SUPPLEMENTAL GROUND TO BE SIZED EQUAL TO GROUNDING ELECTRODE CONDUCTOR.
2. BLUE WIRE NUTS TO BE USED FOR MULTIPLES AS LISTED.
3. ONLY ONE TERMINATION PER LUG
4. SUPPORT M/C CABLE WITHIN 12" OF CANS

DO NOT ENERGIZE LIGHT POLES DO NOT COVER CANS.