Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/17/2006 | MECHANICAL - INTERMEDIATE | Approved | IVRS - Inspection :* OK FOR CEILING TILES |
|
| 04/27/2006 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection :* EXHAUST DUCT & FANS IN RESTROOMS OK TO SHEETROCK. WILL CHECK SUPPLY FROM OVERHEAD. PROVIDE DUCT SMOKE DETECTORS WITH AUDIBLE & VISIBLE ALARMS. USE SHEET METAL HANGER STRAPS ON ALL SHEET METAL DUCTS. NYLON STRAP IS ONLY TO BE USED ON FLEX DUCT. PROVIDE MIN. R-5 INSULATION ON ALL DUCT INSIDE THE BLDG. 1 1/2" FOIL WRAP IS R4.2 INSTALLED. |