Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/23/2006 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* OK FINAL |
|
| 05/22/2006 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. EXIT LIGHTING TO BE ON CIRCUIT SERVING AREA 700.12 2. ONLY ONE CONDUCTOR TERMINATION PER LOG 3. APPROVED EXTENDER RINGS NEEDED FOR BOXES MORE THAN 1/4" FROM BOX TO SURFACE. 314.20 ROOF: 1. TIGHTEN LOOSE FITTINGS. 2. MAINTAIN WORKING CLEARANCES IN FRONT OF DISCONNECTS. 3. BOND ENCLOSURES. |
|
| 05/18/2006 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* OK ABOVE CEILING INSPECTIONS. |