Permit: T06CM01281

Parcel: 115061580


Addresses:

1893 N 11TH AV #200

Inspection Status: Approved

Inspection History: ELECTRIC - CABLE DROP

Date Description Inspector Results Comments
12/07/2006 ELECTRIC - CABLE DROP Approved IVRS - Inspection :*
12/05/2006 ELECTRIC - CABLE DROP Not ready for Inspection IVRS - Inspection :*
MAKE SURE ALL CORRECTIONS ARE COMPLETE BEFORE YOU CALL IN AND HAVE ALL EQUIPMENT OPEN FOR INSPECTION CORRECTLY ADDRESS EQUIPMENT
11/20/2006 ELECTRIC - CABLE DROP Denied IVRS - Inspection :
The service is not per code.| 210*
IT APPEARS THE SERVICE TRENCH WAS NEVER INSPECTED.
1. BOND GUTTERS - NEC 250.92 (LINE SIDE GUTTERS).
2. IDENTIFY SERVICE DISCONNECTS - NEC 230.80 B AND INSTALL THE UNIT # LABEL.
3. ARRANGE BONDING CONDUCTORS TO PREVENT OBJECTIONABLE CURRENT -- NEC 250.6
4. DIFFERENT SIZED CONDUCTORS NOT ALLOWED UNDER SAME TERMINATION - NEC 110.3 (B), 110.14
5. HAVE UNDERSIZED EQUIPMENT BONDING JUMPERS -
NEC 250.102 C
6. IN LOAD SIDE GUTTER - USE EQUIPMENT GROUND TO GROUND GUTTER AND INSTALL MISSING LOCKNUT -
NEC 250.122
7. GROUND PULL BOX AND USE PROPER STRUT CLAMP -
NEC 110
8. BOND ALL METAL PIPES TO SERVICE -- NEC 250.104
9. BOND BUILDING STEEL -- NEC 250.104
10. HAVE OVERFUSED FEEDERS - NEC 310
11. TIGHTEN ALL CONNECTIONS.
12. CAN'T READ CONDUCTOR MARKING.