Permit: T06CM01280

Parcel: 115061580


Addresses:

1893 N 11TH AV #100

Inspection Status: Approved

Inspection History: ELECTRIC - ABOVE CEILING

Date Description Inspector Results Comments
12/22/2006 ELECTRIC - ABOVE CEILING Approved IVRS - Inspection :*
12/13/2006 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
INSPECTION FOR LOWER LEVEL SUSPENDED CEILING ONLY.

1. SUPPORT WIRING OFF GRID -- NEC 300.11
2. IDENTIFY AIR HANDLER SERVICE LABEL
3. IDENTIFY DISCONNECT AND INSTALL FUSES
4. GRID SUPPORT WIRES NOT ALLOWED TO SUPPORT OTHER EQUIPMENT.
OK TO INSTALL TILES AFTER CORRECTIONS -- WILL CHECK ON FINAL