Permit: T06CM01274

Parcel: 136081630

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
03/22/2006 ELECTRIC - FINAL Approved IVRS - Inspection :*
03/21/2006 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. SCH 40 PVC IS NOT ACCEPTABLE FOR EXPOSED WORK
2. INSTALL GROUND WIRE ON OPPOSITE SIDE OF ACORN BELT
3. EMT CONNECTOR IS NOT AN ACCEPTABLE CONDUIT ENTRY IN LB THE WAY THAT YOU HAVE THIS INSTALLED.
4. MOVE G.E.C DIRECTLY TO NEUTRAL BUS BAR
5. USE ANTI-OXIDATION PASTE OR ALUM. CONDUCTORS
6. INSTALL ADDRESS AT METER PER TEP & IRC