Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
Permit Number - T06CM01270
Inspection Description - MECHANICAL - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/25/2006 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* | |
08/24/2006 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* CONDENSATE HOSE OR FAN COIL IS KINKED. DRAIN LINES MUST HAVE A MIN. 1/8" PER FT. SLOPE. CONDENSATE LINES ON ROOF NEED LATEX PAINT. VENTS MUST BE DOWNSTREAM OF THE TRAP. LOW VOLTAGE WIRE MUST BE IN CONDUIT. PROVIDE SCREEN IN T-TOP ON ROOF. |