Permit: T06CM01270

Parcel: 136261290

Inspection Status: Approved

Inspection History: MECHANICAL - ABOVE CEILING

Permit Number - T06CM01270

Inspection Description - MECHANICAL - ABOVE CEILING

Inspection Status - Approved

Date Description Inspector Results Comments
08/17/2006 MECHANICAL - ABOVE CEILING Approved IVRS - Inspection :*
USE A FITTING TO CONNECT CONDENSATE DRAIN TO PVC.
PROVIDE AN AUDIBLE ALARM FOR DUCT SMOKE DETECTOR.
WILL CHECK ON FINAL.
08/16/2006 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
SUPPORT CONDENSATE DRAIN EVERY 4'
BE SURE DRAIN SLOPES MIN. 1/8" PER FT.
ON FINAL PROVIDE A VISIBLE & AUDIBLE ALARM INSIDE THE BUILDING.
DO NOT USE NYLON BANDS TO SUPPORT REFER LINES.