Inspection History: MECHANICAL - ABOVE CEILING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/17/2006 | MECHANICAL - ABOVE CEILING | Approved | IVRS - Inspection :* USE A FITTING TO CONNECT CONDENSATE DRAIN TO PVC. PROVIDE AN AUDIBLE ALARM FOR DUCT SMOKE DETECTOR. WILL CHECK ON FINAL. |
|
| 08/16/2006 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* SUPPORT CONDENSATE DRAIN EVERY 4' BE SURE DRAIN SLOPES MIN. 1/8" PER FT. ON FINAL PROVIDE A VISIBLE & AUDIBLE ALARM INSIDE THE BUILDING. DO NOT USE NYLON BANDS TO SUPPORT REFER LINES. |