Inspection Status: Approved
Inspection History: MECHANICAL - ABOVE CEILING
Permit Number - T06CM01270
Inspection Description - MECHANICAL - ABOVE CEILING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/17/2006 | MECHANICAL - ABOVE CEILING | Approved | IVRS - Inspection :* USE A FITTING TO CONNECT CONDENSATE DRAIN TO PVC. PROVIDE AN AUDIBLE ALARM FOR DUCT SMOKE DETECTOR. WILL CHECK ON FINAL. |
|
08/16/2006 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* SUPPORT CONDENSATE DRAIN EVERY 4' BE SURE DRAIN SLOPES MIN. 1/8" PER FT. ON FINAL PROVIDE A VISIBLE & AUDIBLE ALARM INSIDE THE BUILDING. DO NOT USE NYLON BANDS TO SUPPORT REFER LINES. |