Permit: T06CM01270

Parcel: 136261290

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Permit Number - T06CM01270

Inspection Description - PLUMBING - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
08/25/2006 PLUMBING - FINAL Approved IVRS - Inspection :*
RECEIVED (3) IN HOUSE BACKFLOW CERTIFICATIONS.
08/24/2006 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
1. PROVIDE MINIMUM 1" AIR GAP FOR INDIRECT DRAINS TO FLOOR SINK AT FOUNTAIN DISPENSER.
2. ONLY (1) WATER SUPPLY CAN BE SERVICES DOWN STREAM OF A BACKFLOW DEVICE (NO TEE CONNECTIONS) AT SODA DISPENSER SYSTEM.