Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/16/2006 | MECHANICAL - INTERMEDIATE | Approved | ||
| 06/27/2006 | MECHANICAL - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) CANNOT CONFIRM METAL FRAMED WALLS. HOOD MUST BE MINIMUM 18" FROM WOOD FRAMED STRUCTURE 2) FIRE WRAP TO EXTEND TO TOP OF CURB 3) SECURE FIRE WRAP TO TOP OF HOOD AS PER INSTALL INSTRUCTIONS 4) SCHEDULE FRAMING INSPECTION 5) PAINT EXPOSED BLACK IRON ON ROOF |