Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T06CM01259
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/06/2006 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 06/05/2006 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. SUPPORT ALL LOW VOLTAGE WIRING OFF GRID. 2. EQUIPMENT GROUND TO WATER HEATER IS UNDERSIZED. 3. IDENTIFY PANEL DIRECTORY. 4. REAR EXIT SIGN NOT LIGHTING. |
|
| 05/31/2006 | ELECTRIC - FINAL | Denied | IVRS - Inspection : There is no access to the site.| 920* DOOR IS LOCKED |