Permit: T06CM01259

Parcel: 11521017H

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T06CM01259

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
06/06/2006 ELECTRIC - FINAL Approved IVRS - Inspection :*
06/05/2006 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. SUPPORT ALL LOW VOLTAGE WIRING OFF GRID.
2. EQUIPMENT GROUND TO WATER HEATER IS UNDERSIZED.
3. IDENTIFY PANEL DIRECTORY.
4. REAR EXIT SIGN NOT LIGHTING.
05/31/2006 ELECTRIC - FINAL Denied IVRS - Inspection :
There is no access to the site.| 920*
DOOR IS LOCKED