Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/05/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 09/04/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* FINISH #1 OF PREVIOUS INSPECTION |
|
| 06/07/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. BOXES MORE THAN 1/4" FROM BOX TO SURFACE NEED AN APPROVED EXTENDER RING 314.20 2. IDENTIFY BREAKERS AND CIRCUIT DIRECTORY PER 408.4 3. MAINTAIN WORKING CLEARANCE 110.26 |
|
| 10/25/2006 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* WING B -- RESTROOM OK FINAL -- 1ST PHASE OK |