Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/30/2006 | MECHANICAL - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 06/27/2006 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) CONDENSATE PAN NOT SECURE 2) EXTEND DRYER VENT UP INTO T-TOP |
|
| 06/26/2006 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
| 06/21/2006 | MECHANICAL - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* FURN. B-1 VENT PIPE 1. 12" SUPPLY FLEX DUCT IN CONTACT W/VENT PIPE ASSY. REROUTE AS NECESSARY. 2. CHECK REFRIG. LINES AT TOP REAR PLATE. CU IN CONTACT W/STEEL STRAP. |