Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/15/2006 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 05/09/2006 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 05/08/2006 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* ALL BREAKERS TO BE GENERAL ELECTRIC. |
|
| 05/04/2006 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. USE GE BREAKER FOR PANEL, NOT SIEMENS 2. USE 30 AMP, NOT 40 AMP 3. IDENTIFY WATER HEATER ON CKT NUMBERS 9&11 IN PANEL DIRECTORY, NOT #7 |
|
| 04/25/2006 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. WATER HEATER EQUIPMENT GROUND NOT CONNECTED. 2. I COULD NOT LOCATE OVERCURRENT DEVICE FOR HEATER NEED 2 POLE 30 AMP. BREAKER OR 30 AMP. FUSES AND PROPERLY IDENTIFIED. |