Permit: T06CM01234

Parcel: 122173920

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
05/15/2006 ELECTRIC - FINAL Approved IVRS - Inspection :*
05/09/2006 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
05/08/2006 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
ALL BREAKERS TO BE GENERAL ELECTRIC.
05/04/2006 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. USE GE BREAKER FOR PANEL, NOT SIEMENS
2. USE 30 AMP, NOT 40 AMP
3. IDENTIFY WATER HEATER ON CKT NUMBERS 9&11 IN PANEL DIRECTORY, NOT #7
04/25/2006 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. WATER HEATER EQUIPMENT GROUND NOT CONNECTED.
2. I COULD NOT LOCATE OVERCURRENT DEVICE FOR HEATER NEED 2 POLE 30 AMP. BREAKER OR 30 AMP. FUSES AND PROPERLY IDENTIFIED.