Inspection History Details
Inspection Status: Approved
Inspection History: BUILDING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/02/2010 | BUILDING - FINAL | Approved | IVRS - Inspection :* | |
| 11/29/2010 | BUILDING - FINAL | Partial Approval | IVRS - Inspection :* 1) STUCCO CERT 2) ORIGINAL DBL STAMP CERT FOR POST TENSION SLAB |
|
| 11/22/2010 | BUILDING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) POST ENERGY CERT AT ELECTRIC 2) IF NON METALIC WATER PIPING IS USED, POST AT PANEL 3) REPAIR FIREWALL AT CEILING ABOVE GARAGE WATER HEATER 4) MAX OVER CURRENT PROTECTION OF 40 AMPS FOR EAST A/C COMPRESSOR 5) WIRE GARAGE DISPOSAL UNDER SINK 6) DRIP LEG NEEDED AT FURNACE GAS LINES |
|
| 11/12/2010 | BUILDING - FINAL | Not ready for Inspection | IVRS - Inspection :* |