Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/22/2006 | ELECTRIC - ABOVE CEILING | Approved | ||
| 04/05/2006 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* OK TO COVER ELECTRICAL *NOTE - MAKE L.B. IN WALL FOR PANEL FEEDER ACCESSIBLE |
|
| 04/03/2006 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. FEEDER FOR NEW PANEL "C" NEED TO BE IN A RACEWAY OR CABLE SYSTEM - NEC 300.3 2. INSTALL J-BOX COVERS FOR CAVS 3. INSTALL NAIL PLATES AS NEEDED - 1 1/4" FROM STUD FACE AND LESS NEC 300.4 |