Inspection History Details
Inspection Status: Approved
Inspection History: FRAMING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/27/2006 | FRAMING | Approved | IVRS - Inspection :* | |
| 06/19/2006 | FRAMING | Partial Approval | IVRS - Inspection :* 1) NEED TO INSPECT MESH BEFORE INSULATION |
|
| 06/09/2006 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. SECURE ELECTRIC ROMEX WITHIN 12" OF BOXES. 2. J-BOXES TO BE ACCESSIBLE. 3. FILL IN EXISTING WINDOW WITH WOOD FRAMING PER PLAN. 4. GROUND ALL METAL BOXES (ELECTRIC). 5. ARC-FAULT ALL ELECTRIC CIRCUITS PER PLAN. 6. REMOVE ALL FOAM EXTERIOR TO INSPECT O.S.B SHEATHING (PAPER ALSO). 7. ALL BOTTOM WOOD PLATES TO BE TREATED. 8. FIRE BLOCK CLOSET FURR DOWN 9. STOPPED INSPECTION. |