Permit: T06CM01196

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
09/06/2006 MECHANICAL - FINAL Approved IVRS - Inspection :*
09/01/2006 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
1/2" ID X 24" GAS FLEX CONNECTORS NOT ADEQUATE FOR 175,000 BTU MAKE UP AIR UNITS.
- RELOCATE GAS SHUT OFF VALVE FOR MAU 1.
- PLUGS MISSING FROM MAU DRAIN PANS.
08/25/2006 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
PROVIDE GAS LINES TO UNIT HEATER & ROOFTOP EQUIPMENT VENT CAP MISSING FROM PAN WASHER. PERMANENTLY IDENTIFY ALL EQUIPMENT. CHECKED FIRE WRAP OK TO CLOSE CEILING.