Permit: T06CM01196

Inspection Status: Approved

Inspection History: MECHANICAL - ABOVE CEILING

Date Description Inspector Results Comments
08/23/2006 MECHANICAL - ABOVE CEILING Approved IVRS - Inspection :*
08/01/2006 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
OK FOR CEILING TILES BAKERY SALED & BAKERY. LEAVE OUT @ DISHWASHER NEED TO SEE B VENT FOR DISHWASHER, CONDENSATE LINES CONNECTED ABOVE BAKERY. OK FOR CEILING TILES PRODUCE AREA. PLANS REQUIRE STAINLESS STEEL ON PAN WASHER HOOD. NEED TO SEE VAPOR DUCT FROM OVEN.
07/27/2006 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
- CHECKED FIRE WRAP & CLEANOUT
- OK CEILING TILES PRODUCT PREP, CHECKED EXHAUST TO MEAT DEPT, DELI & MEAT RACKS.
- INSULATE ALL CONDENSATE DRAINS AS PER MP1.1 NOTE 1.19
06/14/2006 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
SUSPENDED ROUGH R.A DUCTS ABOVE GENERAL PRODUCE AREA PROVIDE REQUIREMENT FOR INSULATION. OK TO PROCEED WITH GRID. SUPPLY & RETURN DUCT EMPLOYEE LOUNGE PROVIDE CONDENSATE DRAIN & INSULATION REQUIREMENT.
06/07/2006 MECHANICAL - ABOVE CEILING Not ready for Inspection IVRS - Inspection :*
05/24/2006 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
OK FOR CEILING TILES CUSTOMER SERVICE.
05/15/2006 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
SUSPENDED ROUGH DUCT EMPLOYEE LOUNGE OK TO PROCEED. OK TO SHEETROCK RESTROOMS.