Inspection History Details
Permit: T06CM01196
Inspection Status: Approved
Inspection History: PLUMBING - GAS PRESSURE TEST
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/23/2006 | PLUMBING - GAS PRESSURE TEST | Approved | AFTER HOURS INSPECTION CHECK #25437 30 PSI TEST FROM ANSUL SHUT OFF VALVE IN CEILING DOWN TO SHUT OFFS FOR APPLIANCES IN DELI OK 1. SECURE OVERHEAD GAS PIPING TO UNISTRUTS. 2. PROVIDE SAFETY CABLES FOR APPLIANCES IN DELI. |
|
| 07/25/2006 | PLUMBING - GAS PRESSURE TEST | Approved | 1. GAS TEST FROM BAKERY TO WATER HEATER OK | |
| 07/17/2006 | PLUMBING - GAS PRESSURE TEST | Partial Approval | IVRS - Inspection :* AFTER HOURS INSPECTION CHECK #5533726387 3" FROM METER PER PLAN FOR BAKERY AREA MINUS (1) RACK OVEN ON SOUTHSIDE, WATER HEATER, (4) ROOFTOP UNITS PARTIAL PRESSURE TEST. 1. WILL NEED TO RETEST WHEN SOUTH OVEN PIPING INSTALLED. |
|
| 07/14/2006 | PLUMBING - GAS PRESSURE TEST | Partial Approval | IVRS - Inspection :* 3/4 GAS FROM ABOVE CEILING TO PANWASHER STUB OUT 3/4 GAS FROM ABOVE CEILING TO DONUT FRYER STUB OUT 20 PSI TEST |