Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit: T06CM01196

Inspection Status: Approved

Inspection History: PLUMBING - GAS PRESSURE TEST

Date Description Inspector Results Comments
08/23/2006 PLUMBING - GAS PRESSURE TEST Approved AFTER HOURS INSPECTION CHECK #25437
30 PSI TEST FROM ANSUL SHUT OFF VALVE IN CEILING DOWN TO SHUT OFFS FOR APPLIANCES IN DELI OK
1. SECURE OVERHEAD GAS PIPING TO UNISTRUTS.
2. PROVIDE SAFETY CABLES FOR APPLIANCES IN DELI.
07/25/2006 PLUMBING - GAS PRESSURE TEST Approved 1. GAS TEST FROM BAKERY TO WATER HEATER OK
07/17/2006 PLUMBING - GAS PRESSURE TEST Partial Approval IVRS - Inspection :*
AFTER HOURS INSPECTION CHECK #5533726387
3" FROM METER PER PLAN FOR BAKERY AREA MINUS (1) RACK OVEN ON SOUTHSIDE, WATER HEATER, (4) ROOFTOP UNITS PARTIAL PRESSURE TEST.
1. WILL NEED TO RETEST WHEN SOUTH OVEN PIPING INSTALLED.
07/14/2006 PLUMBING - GAS PRESSURE TEST Partial Approval IVRS - Inspection :*
3/4 GAS FROM ABOVE CEILING TO PANWASHER STUB OUT
3/4 GAS FROM ABOVE CEILING TO DONUT FRYER STUB OUT
20 PSI TEST