Inspection History Details
Permit: T06CM01196
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/08/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 09/12/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* NEED PLAN CHECK CITY APPROVAL STAMP |
|
| 06/28/2007 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* NEED CITY APPROVED STAMP -- STANTEC DID THIRD PARTY |
|
| 09/13/2006 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
| 08/31/2006 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* | |
| 08/28/2006 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* CANCELLED BY TOM |
|
| 08/25/2006 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* FINISH UPSTAIRS SERVICE FINISH LB FITTING DELI WAITING ON BACK ORDER PARTS OK PANEL "CL" |
|
| 08/23/2006 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* OK DELI SUBJECT TO OTHERS 1. FINISH PREVIOUS INSPECTIONS RECEIVED MONEY ORDER #55584289057 $108.00 |
|
| 08/23/2006 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* CANCELLED BY TODD |
|
| 08/21/2006 | ELECTRIC - FINAL | Partial Approval | REC'D CHECK #25436 $163.00 1. FINISH VDV BEER & WINE, ISLE, CASHIER, SERVICE HALL 2. FINISH ELECTRIC NEXT TO PANEL BA AT CEILING 3. USE APPROVED FITTING WITH LB 4. FINISH SEALING 300.7 REFRIGERATOR, DELI 5. KITCHEN RECEPTACLES FOR GENERAL USE TO BE GFCI 210.8 6. OLD PANEL CL TO HAVE NEW JUNCTION BOX COVER 7. SUPPORT BATH EXHAUST FAN JUNCTION BOX 8. FINISH ROOF BUSHINGS AS DISCUSSED. |
|
| 08/21/2006 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* CANCELLED BY TOM |
|
| 08/17/2006 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1. CANNOT ACCESS PANEL -- MAINTAIN WORKING CLEARANCE 2. MAINTAIN SURFACE CONTACT (T-2) FOR GROUND LUG 3. VERIFY TAP RULES 240.21 4. MISSING JUNCTION BOX COVERS OK ROOF DISCONNECTS A/C |
|
| 08/16/2006 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* CANCELLED BY TOM |
|
| 08/15/2006 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
| 08/10/2006 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* CANCELLED BY TOM |
|
| 08/09/2006 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1. FINISH DEMO 2. FINISH ABOVE CEILING DELI |
|
| 08/08/2006 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. RECEPTACLE COVERS BELOW SINKS IN WET LOCATION NEED TO BE FOR WET LOCATION. 2. RE-SUPPORT M/C & CAN ABOVE CEILING AT DELI OK DELI TEMP OCCUPANCY RECEIVED CHECK #25270 FOR $108.00 |
|
| 08/07/2006 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1. FINISH VDV ABOVE SERVICE HALL 2. FINISH NEXT TO PANEL "BA" AT CEILING 3. SUPPORT VDV ABOVE WATER & BEER AISLES |
|
| 08/06/2006 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 2036 2090 OK NORTH (HOOD) DELI WALL RECEIVED CHECK #25272 FOR $108.00 |
|
| 08/04/2006 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* | |
| 08/03/2006 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* OK CASHIER STANDS OK 3 - 3/4" & 1 - 1" PVC UNDER DELI OK WINDOW DELI OK BAKERY SUBJECT TO OTHER INSPECTIONS 1. SAFEWAY PERSONNEL NOT TO BE OPERATING IN CONSTRUCTION AREA. 2. SUPPORT VDV CABELING ABOVE CASHIERS RECEIVED CHECK 25273 FOR $108.00 |
|
| 08/02/2006 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* | |
| 08/01/2006 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1. MAINTAIN WORKING CLEARANCE IN FRONT OF CONTROL PANEL. 2. FINISH VDV CABELING 3. MAINTAIN WORKING CLEARANCE WATER CHILLER 4. FILLER BLANKS IN PANELS 5. SUPPORT ANSUL CONDUIT ABOVE GRID AND ON WALL 6. FINISH SUPPORTS TO CORD DROPS. RECEIVED MONEY ORDER #55584286434 FOR $108.00 |
|
| 06/23/2006 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* | |
| 06/22/2006 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* |
|
| 06/21/2006 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* |
|
| 06/16/2006 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. CIRCUIT DIRECTORY STILL NOT LABELED - ALSO PANEL ON OUTSIDE OF COVER. 2. WHERE IS MAIN BONDING JUMPER SECONDARY SIDE OF TRANSFORMER? 3. MANUFACTURERS LABELING REQUIRE ALL FIELD WIRING BELOW ARROWS. 4. PLEASE DE-ENERGIZE UNTIL CORRECTIONS ARE MADE. |
|
| 06/15/2006 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* OK TO TILE RESTROOM CORRIDOR & BREAKROOM 1. FIXTURES TO BE SECURELY ATTACHED TO GRID 410.16 IF SCREWS 4 ON CORNERS OR 2 ON CENTERS. 2. ONLY ONE CONDUCTOR PER TERMINATION AT LUGS. 3. PROTECT CONDUCTORS #4 & LARGER AT FITTINGS. 4. GROUNDING FOR TRANSFORMER TO BE ATTACHED TO CASE NOT SUPPORT FOOT. 5. LABEL CIRCUIT BREAKER. 6. CLEAN EXCESS FOREIGN MATERIAL OUT OF PANEL. |
|
| 06/14/2006 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* | |
| 05/11/2006 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* |