Permit: T06CM01196

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
08/31/2006 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
08/17/2006 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
08/07/2006 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
08/06/2006 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
08/04/2006 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
08/02/2006 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK ROOF EXHAUST WITH BAKERY & BATHROOMS
1. DISCONNECTING MEANS NOT TO BE ON ACCESSIBLE PANELS SCREWS ARE PRESENT (440.14)
08/01/2006 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
07/27/2006 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK CANS & 2X2 MEAT CASES
OK BACK WALLS BAKERY
OK SOUTH HALF PRODUCT CEILING EXCEPT AS NOTED
1. SUPPORT EXISTING VDV CABELING PER 725.3 & 800.3 ALSO SUPPORT AS PER 725.6 & 800.6
2. SUPPORT WIRES TO BE AS PER 300.11
3. MISSING JUNCTION BOX COVERS
4. SUPPORT TRACK LIGHTING 4' INTERVALS
07/14/2006 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
1. CORRECTLY SUPPORT M/C CABLE IN WALL.
2. TIGHTEN LOOSE FITTING
3. SUPPORT M/C WITHIN 12" OF BOXES 334.30
07/03/2006 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK BAKERY WALL
OK KITCHEN WALL BEHIND HOOD
1. NOTE VDV NOT INSTALLED AT THIS TIME.
06/23/2006 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK TO OCCUPY BREAKROOM SUBJECT TO OTHER INSPECTORS
OK CASES PRODUCE & MEAT
06/22/2006 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. MAIN BONDING JUMPER TO BE AS PER 250.30(A)(1)
2. WE STILL HAVE HOTS & NEUTRAL CONNECTED TOGETHER
IF TAPED TO BE FULLY EXPOSED LENGTH.
3. M/C TO BE 12" FROM BOXES & 6' THEREAFTER
06/21/2006 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. GROUNDING ELECTRODE CONDUCTOR TO BE AS PE 250.64(E)
2. MAIN BONDING JUMPER TO BE INSTALL.
3. SUPPORT M/C CABLE SECURELY
4. CORRECTLY IDENTIFY UNGROUNDED OR GROUNED CONDUCTOR.
5. TIGHTEN LOOSE FITTINGS.
6. FILL UNUSED OPENING IN TRANSFORMER
06/14/2006 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
*NOTE: ALL VDV CABELING ABOVE PRODUCE TO BE SUPPORTED ALSO FIXTURES.
OK CUSTOMER SERVICE, FLORAL KIOSK & CASH ROOM
TO OCCUPY PER B. SUBA
1. PROTECT CONDUCTOR #4 & LARGER AT FITTING.
2. CLEAN OUT FOREIGN MATERIAL FROM BOTTOM OF PANEL.
OK LIQUOR CABINET AND BATHROOMS TO OCCUPY.
06/07/2006 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
05/17/2006 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
FLORAL KIOSK, CASHROOM WALLS, CUSTOMER SERVICE WALLS
UG & LIQUOR CABINET.
05/15/2006 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. JUNCTION BOX TO BE ACCESSIBLE.
OK WALLS BATHROOMS & BREAKROOM
OK UNDERGROUND AT CUSTOMER SERVICE
05/11/2006 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. SUPPORT CONDUIT WITHIN 3' OF BOX.
2. IDENTIFY MAIN DISCONNECT ALSO LIST ON SUB-PANEL LOCATION OF MAIN DISCONNECT.
OK TO USE STARBUCKS KIOSK ONLY.
05/10/2006 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*