Inspection History Details
Permit: T06CM01196
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/31/2006 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 08/17/2006 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
| 08/07/2006 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
| 08/06/2006 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
| 08/04/2006 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
| 08/02/2006 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK ROOF EXHAUST WITH BAKERY & BATHROOMS 1. DISCONNECTING MEANS NOT TO BE ON ACCESSIBLE PANELS SCREWS ARE PRESENT (440.14) |
|
| 08/01/2006 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
| 07/27/2006 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK CANS & 2X2 MEAT CASES OK BACK WALLS BAKERY OK SOUTH HALF PRODUCT CEILING EXCEPT AS NOTED 1. SUPPORT EXISTING VDV CABELING PER 725.3 & 800.3 ALSO SUPPORT AS PER 725.6 & 800.6 2. SUPPORT WIRES TO BE AS PER 300.11 3. MISSING JUNCTION BOX COVERS 4. SUPPORT TRACK LIGHTING 4' INTERVALS |
|
| 07/14/2006 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* 1. CORRECTLY SUPPORT M/C CABLE IN WALL. 2. TIGHTEN LOOSE FITTING 3. SUPPORT M/C WITHIN 12" OF BOXES 334.30 |
|
| 07/03/2006 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK BAKERY WALL OK KITCHEN WALL BEHIND HOOD 1. NOTE VDV NOT INSTALLED AT THIS TIME. |
|
| 06/23/2006 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK TO OCCUPY BREAKROOM SUBJECT TO OTHER INSPECTORS OK CASES PRODUCE & MEAT |
|
| 06/22/2006 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. MAIN BONDING JUMPER TO BE AS PER 250.30(A)(1) 2. WE STILL HAVE HOTS & NEUTRAL CONNECTED TOGETHER IF TAPED TO BE FULLY EXPOSED LENGTH. 3. M/C TO BE 12" FROM BOXES & 6' THEREAFTER |
|
| 06/21/2006 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. GROUNDING ELECTRODE CONDUCTOR TO BE AS PE 250.64(E) 2. MAIN BONDING JUMPER TO BE INSTALL. 3. SUPPORT M/C CABLE SECURELY 4. CORRECTLY IDENTIFY UNGROUNDED OR GROUNED CONDUCTOR. 5. TIGHTEN LOOSE FITTINGS. 6. FILL UNUSED OPENING IN TRANSFORMER |
|
| 06/14/2006 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* *NOTE: ALL VDV CABELING ABOVE PRODUCE TO BE SUPPORTED ALSO FIXTURES. OK CUSTOMER SERVICE, FLORAL KIOSK & CASH ROOM TO OCCUPY PER B. SUBA 1. PROTECT CONDUCTOR #4 & LARGER AT FITTING. 2. CLEAN OUT FOREIGN MATERIAL FROM BOTTOM OF PANEL. OK LIQUOR CABINET AND BATHROOMS TO OCCUPY. |
|
| 06/07/2006 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* | |
| 05/17/2006 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* FLORAL KIOSK, CASHROOM WALLS, CUSTOMER SERVICE WALLS UG & LIQUOR CABINET. |
|
| 05/15/2006 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. JUNCTION BOX TO BE ACCESSIBLE. OK WALLS BATHROOMS & BREAKROOM OK UNDERGROUND AT CUSTOMER SERVICE |
|
| 05/11/2006 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. SUPPORT CONDUIT WITHIN 3' OF BOX. 2. IDENTIFY MAIN DISCONNECT ALSO LIST ON SUB-PANEL LOCATION OF MAIN DISCONNECT. OK TO USE STARBUCKS KIOSK ONLY. |
|
| 05/10/2006 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* |