Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - HOODS
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/30/2006 | MECHANICAL - HOODS | Approved | ||
| 08/18/2006 | MECHANICAL - HOODS | Partial Approval | IVRS - Inspection :* FIRE WRAP UP INTO CURBS, OK SEAL TOP. EX. DUCT AND SET BLOWERS |
|
| 08/11/2006 | MECHANICAL - HOODS | Partial Approval | IVRS - Inspection :* FINISH FIRE WRAP ON DUCT INSIDE CURBS. EXTEND LARGE CURB & GREASE DUCT FAN TO TERMINATE AT TOP OF WALL IF WITHIN 10' |
|
| 08/03/2006 | MECHANICAL - HOODS | Denied | IVRS - Inspection : See detailed listing on site.| 999* FIRE WRAP NOT INSTALLED PER INSTALL INSTRUCTIONS REMOVE ALL TAPE FROM JOINTS & SEAMS PROVIDE MIN. 3" OVERLAP BANDING NOT CORRECT FLEX DUCT NOT STRAPPED PER INSTALL INSTRUCTIONS OR PER PLANS. DUCT SMOKE DETECTORS MUST BE ABOVE ALL INLETS OR PLENUM. |
|
| 08/02/2006 | MECHANICAL - HOODS | Cancelled | CANCELLED BY CALVIN | |
| 07/25/2006 | MECHANICAL - HOODS | Partial Approval | IVRS - Inspection :* |