Permit: T06CM01191

Parcel: 11205283F


Addresses:

2970 N CAMPBELL AV

Inspection Status: Approved

Inspection History: MECHANICAL - HOODS

Date Description Inspector Results Comments
08/30/2006 MECHANICAL - HOODS Approved
08/18/2006 MECHANICAL - HOODS Partial Approval IVRS - Inspection :*
FIRE WRAP UP INTO CURBS, OK
SEAL TOP. EX. DUCT AND SET BLOWERS
08/11/2006 MECHANICAL - HOODS Partial Approval IVRS - Inspection :*
FINISH FIRE WRAP ON DUCT INSIDE CURBS.
EXTEND LARGE CURB & GREASE DUCT FAN TO TERMINATE AT TOP OF WALL IF WITHIN 10'
08/03/2006 MECHANICAL - HOODS Denied IVRS - Inspection :
See detailed listing on site.| 999*
FIRE WRAP NOT INSTALLED PER INSTALL INSTRUCTIONS
REMOVE ALL TAPE FROM JOINTS & SEAMS
PROVIDE MIN. 3" OVERLAP
BANDING NOT CORRECT
FLEX DUCT NOT STRAPPED PER INSTALL INSTRUCTIONS OR PER PLANS.
DUCT SMOKE DETECTORS MUST BE ABOVE ALL INLETS OR PLENUM.
08/02/2006 MECHANICAL - HOODS Cancelled CANCELLED BY CALVIN
07/25/2006 MECHANICAL - HOODS Partial Approval IVRS - Inspection :*