Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - ABOVE CEILING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/30/2006 | MECHANICAL - ABOVE CEILING | Approved | ||
| 08/03/2006 | MECHANICAL - ABOVE CEILING | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 08/02/2006 | MECHANICAL - ABOVE CEILING | Cancelled | CANCELLED BY CALVIN | |
| 07/25/2006 | MECHANICAL - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :* YOU CANNOT USE CHAIN, PLUMBERS TAPE OR WIRE TO STRAP DUCT. CHECKED WELDS ON GREASE DUCTS, OK TO FIRE WRAP DUCT SMOKE DETECTORS TO BE INSTALLED IN THE RETURN DUCT NOT THE SUPPLY DUCT. OFFSET GREASE DUCT TO FIT CENTER OF CURB. |