Permit: T06CM01191

Parcel: 11205283F


Addresses:

2970 N CAMPBELL AV

Inspection Status: Approved

Inspection History: PLUMBING - ROUGH, SOIL

Date Description Inspector Results Comments
05/12/2006 PLUMBING - ROUGH, SOIL Approved IVRS - Inspection :*
1. ABS DWV UNDERSLAB OK TO COVER.
GREASE WASTE TO OUTSIDE AND G.T DISCHARGE UNDER BLDG. TO P.O.C OK
2. GAS INSTALLED UNDER BLDG. PER PLAN OK
TEST OK
3. ONE COPPER LOOP OK
4. OK FOR CONCRETE.
05/08/2006 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection :*
WATER TEST UNDERGROUND SANITARY DRAINAGE ONLY OK
1. NEED TO SEE INSTALL OF UNDERSLAB WATER.
2. NEED TO SEE PIPE WRAPS PRIOR TO CONCRETE WITH INSTALL OF FLOOR SINKS.
3. NEED TO SEE GREASE WASTE INSTALL.
4. NEED TO SEE ALL DEMO CAPPING.
05/07/2006 PLUMBING - ROUGH, SOIL Not ready for Inspection IVRS - Inspection :*
1. POINT OF VENT MAY NOT BE BELOW THE TRAP WEIR.
2. TRAP ARM TO BE 2X THE PIPE DIAMETER.
05/04/2006 PLUMBING - ROUGH, SOIL Not ready for Inspection IVRS - Inspection :*
1. NOT INSTALLED PER PLAN.
2. BACKPITCHED SECTIONS NOT APPROVED.
3. REQUIRE 2X PIPE DIAMETER FROM POINT OF VIEW TO WIER OF TRAP.
4. POINT OF VENT MAY NOT BE BELOW THE TRAP WEIR.