Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/04/2006 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 09/01/2006 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* | |
| 08/30/2006 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
| 08/29/2006 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1. PANEL DIRECTORIES ARE STILL NOT CORRECTLY IDENTIFIED 2. PAY RE-INSPECTION FEE 3. MAKE SURE ALL CORRECTIONS COMPLETE ON ROOF AND PROVIDE A LADDER FOR ME. THEN CALL FOR FINAL -- OK TO OCCUPY |
|
| 08/25/2006 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* PARTIAL INSPECTION ONLY 1. EMERGENCY LIGHTING NOT WORKING/NOT PER PLAN NEC 700.12 (E) 2. PANEL DIRECTORIES ARE NOT CORRECTLY IDENTIFIED AND ARE NOT LEGIBLE - NEC 408.4 ALSO MAKE PANEL DIRECTORY MORE PERMANENT. 3. HAVE LOOSE/REVERSE POLARITY @ BOOTH RECEPTACLE NEC 110.3 4. PROVIDE GFI PROTECTION FOR BATHROOM RECEPTACLE NEC 210.8(B) 5. PROVIDE A DISCONNECTING MEANS FOR FOOD WARMER NEC 422.30 6. ISLAND OUTLET BOX IS LOOSE, UNGROUNDED, AND OVERFILLED - NEC 314, 250, 110 7. SEAL RACEWAY TO WALK IN -- NEC 300.7 ON ROOFTOP 8. IDENTIFY ALL DISCONNECTS AND UNITS 9. DISCONNECTS NOT GROUNDED OR WIRES PROPERLY 10. PROVIDE SERVICE OUTLET - NEC 210.63 |
|
| 08/23/2006 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* WORK IN PROGRESS |