Permit: T06CM01191

Parcel: 11205283F


Addresses:

2970 N CAMPBELL AV

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
09/04/2006 ELECTRIC - FINAL Approved IVRS - Inspection :*
09/01/2006 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
08/30/2006 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
08/29/2006 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1. PANEL DIRECTORIES ARE STILL NOT CORRECTLY IDENTIFIED
2. PAY RE-INSPECTION FEE
3. MAKE SURE ALL CORRECTIONS COMPLETE ON ROOF AND PROVIDE A LADDER FOR ME.

THEN CALL FOR FINAL -- OK TO OCCUPY
08/25/2006 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
PARTIAL INSPECTION ONLY
1. EMERGENCY LIGHTING NOT WORKING/NOT PER PLAN
NEC 700.12 (E)
2. PANEL DIRECTORIES ARE NOT CORRECTLY IDENTIFIED AND ARE NOT LEGIBLE - NEC 408.4 ALSO MAKE PANEL DIRECTORY MORE PERMANENT.
3. HAVE LOOSE/REVERSE POLARITY @ BOOTH RECEPTACLE NEC 110.3
4. PROVIDE GFI PROTECTION FOR BATHROOM RECEPTACLE NEC 210.8(B)
5. PROVIDE A DISCONNECTING MEANS FOR FOOD WARMER
NEC 422.30
6. ISLAND OUTLET BOX IS LOOSE, UNGROUNDED, AND OVERFILLED - NEC 314, 250, 110
7. SEAL RACEWAY TO WALK IN -- NEC 300.7

ON ROOFTOP
8. IDENTIFY ALL DISCONNECTS AND UNITS
9. DISCONNECTS NOT GROUNDED OR WIRES PROPERLY
10. PROVIDE SERVICE OUTLET - NEC 210.63
08/23/2006 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
WORK IN PROGRESS