Permit: T06CM01191

Parcel: 11205283F


Addresses:

2970 N CAMPBELL AV

Inspection Status: Approved

Inspection History: ELECTRIC - ABOVE CEILING

Date Description Inspector Results Comments
09/04/2006 ELECTRIC - ABOVE CEILING Approved IVRS - Inspection :*
08/15/2006 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
1. CLOSE OFF ALL UNUSED OPENINGS AND INSTALL COVERS IN J-BOXES
2. EACH FIXTURE/TRACK LIGHT NEEDS TO HAVE A SEISMIC WIRE ATTACHED, TO STRUCTURE AND FIXTURE BRACKET ALSO SUPPORT BAT PACKS OFF GRID (EMERGENCY PACKS) OK TO COVER CEILING AFTER CORRECTIONS COMPLETE.
08/10/2006 ELECTRIC - ABOVE CEILING Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. COMPLETE CORRECTIONS FROM PREVIOUS INSPECTION
2. MUST BE RE-INSPECTION FEE
08/07/2006 ELECTRIC - ABOVE CEILING Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. ALL FIXTURES (LIGHTING) NEED WIRE THAT GOES TO STRUCTURE
2. WIRES THAT SUPPORT MC/RACEWAYS MUST EXTEND TO CEILING GRID.
08/03/2006 ELECTRIC - ABOVE CEILING Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. NEED SUPPORT WIRES FOR ALL LIGHTING FIXTURES AND EXIT SIGNS - ATTACH TO FIXTURE MOUNTING BRACKET OR FIXTURE ITSELF.
2. SUPPORT WIRES FOR RACEWAYS OR FIXTURE WHIPS NEED TO EXTEND TO GRID.
3. TRACK LIGHTING NEED SUPPORT MAX. 4' ON CENTER
4. HAVE OVERFILLED J-BOXES USE BOX EXTENSION AS NEEDED
5. ALL MC MUST TERMINATE WITH MC CONNECTOR GOING INTO J-BOX.
08/02/2006 ELECTRIC - ABOVE CEILING Not ready for Inspection IVRS - Inspection :*
07/25/2006 ELECTRIC - ABOVE CEILING Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
FINISH ALL CEILING WORK BEFORE INSPECTION