Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/04/2006 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 06/19/2006 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK TO COVER ELECTRICAL IN WALLS AND HARD LIDS. *NOTE: MC ABOVE BATHROOMS NEED TO BE STRAPPED WITHIN 12" OF TERMINATIONS TO LIGHTS AND FANS - DO THIS BEFORE FINAL. |
|
| 06/15/2006 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. RECEPTACLES NOT ROUGHED SEE RED CLOUDED AREAS ON PLANS. 2. EXH. FANS IN HARD CEILING ARE NOT WIRED YET. 3. PROPERLY SECURE CONDUITS IN BATHROOM SOUTH WALLS. 4. MC CABLE NEEDS PROPER SUPPORT (WITHIN 12" OF BOXES) 5. E.M.T CONNECTORS LOOSE 6. MC CONNECTOR HAS LOOSE LOCKNUT. 7. SEE WORKMANSHIP. |