Permit: T06CM01186

Parcel: 140263860

Inspection Status: Approved

Inspection History: FRAMING

Permit Number - T06CM01186

Inspection Description - FRAMING

Inspection Status - Approved

Date Description Inspector Results Comments
10/26/2006 FRAMING Approved IVRS - Inspection :*
10/24/2006 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. INSUFFICIENT FALL IN 3" ABS OVER GARAGE
2. FIRESTOP 2ND FLOOR PENETRATIONS.
3. BLOCK MECH.
4. FIRESTOP TRIANGLE NITCH @ ENTRY
5. FRESH AIR INTAKE REQ'S 10' CLEARANCE TO PLUMBING EXHAUST.
6. MECH BOOT OVER KITCHEN OUT OF CEILING
7. REPLACE STUD IN BAY
8. FIRESTOP SUPPLY CHASE
9. STOPPED INSPECTION
10/23/2006 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) NOT READY PER SUPER
10/20/2006 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) NOT READY PER SUPER